Alpha American Co., 10 Industrial Blvd., Palisade, MN 56469www.yukon-eagle.com 1-800-358-0060Oil/Wood - Gas/WoodWarm Air Central Heating FurnacesOWNER
SpecificationsMODEL LWO-112 (Oil)Input rating ...
Questions? Visit www.yukon-eagle.com or call 1-800-358-0060PLAN YOUR INSTALLATIONIt is recommended to read through the entire manualbefore beginning y
Plan Your InstallationFIG. 412ABOVE TOP OFWARM AIR PLENUMFROM THEFRONTFROM SIDESAND BACKFROM CHIMNEYCONNECTOR6 FT OFPLENUM6 FT OFPLENUMCLEARANCES TO C
FIG. 5AIR CONDITIONING COIL MUSTBE INSTALLED WITH A METALCONDENSATE PAN.DO NOT USE PLASTIC PANDUCTS SHOULD BE LARGE ENOUGHTO HANDLE GRAVITY AIR FL
14InstallationFIG. 6FIG. 7PLACE FURNACEReview all instructions in the Planning YourInstallation section. Place the furnace in the pre-selected locatio
InstallationFIG. 9FIG. 10OIL BURNER INSTALLATION• Model LWO-112 burner has a (140,000 BTU input)1.00 G.P.H. 80 degree H nozzle installed at the factor
16InstallationFIG. 11Questions? Visit www.yukon-eagle.com or call 1-800-358-0060DRAW COLLAR (Models LWO-168 & LWG-168 ONLY)Firmly attach the draw
InstallationSMOKE BAFFLESThe smoke baffles are factory installed. Theymust be checked to see that they have notbecome dislodged during shipping. See F
18InstallationFIG. 16FanLimitControlINSTALLING THE HONEYWELL FAN/LIMITCONTROLIncluded in the accessory carton is a white sheet metalbracket that is 8-
Questions? Visit www.yukon-eagle.com or call 1-800-358-0060MOUNTING THE THERMOSTATSThe thermostats must be mounted on an interiorcentrally located wal
2DANGERRISK OF FIRE OR EXPLOSIONDo not burn garbage, gasoline, drain oil, kerosene, thinners, etc.WARNINGRISK OF FIRETightly close the firing door and
20Questions? Visit www.yukon-eagle.com or call 1-800-358-0060FUEL TANKS AND FUEL LINESFuel tanks and fuel lines must be installed inaccordance with re
21InstallationQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060GAS PIPE SIZINGCheck with your local gas supplier to determine total gasload
22InstallationFUME SENSOR (GAS MODELS ONLY)The FUME SENSOR is a manual reset heat/pressuresensor. It will shut down the gas burner. This occurs whenth
ELECTRIC WIRINGAll electrical wiring must be done in accordance with theNational Electrical Code. The code needs to be legallyauthorized in the area w
2424 Volt Field WiringTerminal 2controlsgas/oil burnerthermostatTerminal 1controls wooddamper/woodthermostatRC R Y CWGRC R Y CWGCR12TTOIL or GASBURN
25FIG. 24CAUTION: Do not use any smokepipes less than 24 gauge betweenfurnace and chimney.WARNING: No damper, heat saver, orautomatic vent damper de
InstallationQuestions? Visit www.yukon-eagle.com or call 1-800-358-006026INSTALLATIONInstall barometric draft control using a 24 or 26 gauge8” X 8” X
27PROPER CHIMNEYSThe National Fire Protection Association (NFPA) requires that all factory built chimneys be Listed andinstalled in accordance with co
28InstallationQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060
COMBUSTION AIRMake-up outside air must be provided to furnace forproper fuel combustion. This is provided by openingsto outside of building. These ope
TABLE OF CONTENTSINTRODUCTIONSafety Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30InstallationQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060FURNACE LOCATED IN CONFINED SPACEWhen the furnace is in utility room, install
31Questions? Visit www.yukon-eagle.com or call 1-800-358-0060Operating InstructionsOIL FIRING THE UNITTo start the oil burner on a new installation1.
32Operating InstructionsFIG. 30Gas Firing the UnitTo Start the Gas burner on new installation1. With gas line in “off” position, install burner using
33Operating InstructionsQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060BEST WOOD TO BURNAll solid fuel, whether it is coal, pine, oak or a
34Operating InstructionsIMPORTANT: Keep ash drawer empty.Primary air to the wood chambertravels under the grate. The grates willwarp and eventually b
35Operating InstructionsQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060WHAT SIZE COAL SHOULD I BURN?The air space between the furnace grat
36Questions? Visit www.yukon-eagle.com or call 1-800-358-0060Operating InstructionsOPERATING INSTRUCTIONS FOR BURNING COALON 1/2-INCH OPENING GRATES (
37Questions? Visit www.yukon-eagle.com or call 1-800-358-0060Wiring DiagramsOIL AND WOOD HEATING ONLY
38OIL AND WOOD HEATING WITH A/CWiring Diagrams
39GAS AND WOOD HEATING ONLYWiring Diagrams
DANGERS-CAUTION-FIRE HAZARDS(Burn wood logs or coal only)Do not install a power humidifier on the warm air plenum.Do not load wood above secondary air
GAS AND WOOD HEATING WITH A/C40Wiring Diagrams
MaintenanceGRATE CARE - ASH REMOVALIt is necessary that ashes be removed from the ash panon a daily basis. The ashes should never be allowed toaccumul
MaintenanceSMOKE PIPE, CHIMNEY AND SECONDARYHEAT EXCHANGERDo not burn green or freshly felled wood. This maycause creosote and soot to build up in chi
MaintenanceFURNACE BLOWER ADJUSTMENTSet adjustable motor pulley so blower will giveapproximately 80-90º F temperature rise through furnace.After pulle
HEADINGMaintenanceQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060DUCT WORK AND BLOWER SPEED ADJUSTMENTSupply and return duct system should
45MaintenanceQuestions? Visit www.yukon-eagle.com or call 1-800-358-0060TESTING INSTALLATIONS FOR EFFICIENCYA Draft gauge must be used. Draft in smoke
46MaintenanceTEST PROCEDUREStep 1.Set the thermostat high enough so that the unit will runfor at least 15 minutes, the maximum time that shouldbe requ
MaintenanceFIG. 42FIREBRICK PLACEMENTModels (LWO-112 & LWG-112 ONLY) (Fig. 42)Lower Row1. Place 3 ea. 12”x 6” bricks at rear of firebox2. Place 4
48MaintenanceOIL BURNER MAINTENANCEMAINTENANCE AT THE END OF THE HEATINGSEASON:1. Shut off electric current to burner at fuse panel.2. If oil filter h
MaintenanceHOW TO PREVENT RUST AND CORROSIONAt the end of each heating season, clean both primaryand secondary heat exchangers. Also, clean the ash pa
5Unpack and Check Your CartonsINSPECT SHIPMENTYour furnace is shipped complete in three cartons.Note any damage to the shipping cartons. Remove allite
SMOKE IN THE FURNACE ROOMThis condition is usually caused because smokeis not being drawn up through the chimney. Othercauses could be a failed (fireb
51MaintenanceOVER HEATING WHEN BURNING SOLID FUEL ASYOUR PRIMARY SOURCE OF HEATIf your home is overheating, your furnace is providing heatwhen the the
52Exploded Views & Parts ListEAGLE I - HUSKYMODELS LWO-112 & LWG-112
53REPAIR PARTS-Combustion Chamber Assembly (Left Hand Shown)EAGLE I- HUSKY OIL/GAS-SOLID FUEL COMBINATION FURNACEModels LWO-112 and LWG-112Key No.
54Exploded Views & Parts ListEAGLE II - POLARMODELS LWO-168 & LWG-168
55(Left Hand Shown)EAGLE II - POLAR OIL/ GAS-SOLID FUEL COMBINATION FURNACEModels LWO-168 and LWG-168Key No. Left Hand Right Hand
56Questions? Visit www.yukon-eagle.com or call 1-800-358-0060Exploded Views & Parts ListWAYNE MODEL MSROIL BURNERGUN ASSEMBLY
57BURNER COMPONENTS W A Y N E M O D E L MSRPAR T DE SCRIP TI ON A ND PART NU MB ER W HE N ORDER IN G PAR TSNO. Part
58Exploded Views & Parts ListWAYNE MODEL P250AF-DINGAS BURNER
59BURNER COMPONENTS WAYNE MODEL P250AF-DINKey No. Part Description Part Number1 Control Box Cover ASM 628992 Time Delay Relay 100983-0023 Trans
YUKONTROL SOLID-STATEFURNACE CONTROL This is the solid-statecontrol that coordinates the gas or oil burnerfunction with the wood/coal damper so that y
60Exploded Views & Parts ListTHIS CIRCULATING FAN PERFORMANCE CURVECHART IS FOR DETERMININGMOTOR HORSEPOWER NEEDSCIRCULATING FAN PERFORMANCE CURVE
Exploded Views & Parts ListCIRCULATING FAN PERFORMANCE CURVE CHARTMODELSLWO-168 AND LWG-168THIS CIRCULATING FAN PERFORMANCE CURVECHART IS FOR DETE
Problem: If you do not seem to be getting enough air circulation...Cause: Air filter is dirty Correction: Clean or replace air filter as necessaryTr
63NotesModel Number: __________________________________ Serial Number:__________Installation Date:_______________________Contractor___________________
Alpha American Co., 10 Industrial Blvd., Palisade, MN 56469www.yukon-eagle.comEAGLE OWNER'SMANUAL• Assembly• Installation• Operation• Repair Par
7Furnace Features - Eagle I - Huskyvwxyz{|}~u
8Furnace Features - Eagle II - PolarYUKONTROL SOLID-STATEFURNACE CONTROL This is the solid-statecontrol that coordinates the gas or oil burnerfunction
9Furnace Features - Eagle II - Polarvwyz{x|}u